ESI Digital Status Monitor
Acquires dry contact status from switches, MCBs, cabinet doors or third-party equipment; DI count and contact conditions are confirmed by model
The core of switchgear switch and MCB status monitoring is to connect the available auxiliary contacts, MCB status contacts and cabinet door contacts to ESI, then aggregate them through ESX into FEXLINK to build status-change, alarm and response records. Contact type, voltage level, isolation method and DI count must be confirmed on site first; general digital input monitoring must not be extended into current or temperature monitoring.
The solution suits switchgear retrofits that already have dry contacts but lack remote status records. It focuses on contact wiring, status mapping, event timing and the management loop, and does not change existing breaker protection.
Acquires dry contact status from switches, MCBs, cabinet doors or third-party equipment; DI count and contact conditions are confirmed by model
Aggregates data from multiple ESI units and performs edge buffering, time stamping and upload
Displays cabinet, circuit, point, status-change and alarm response records
Breaker auxiliary contacts, MCB status contacts and cabinet door contacts are wired to ESI.
ESX aggregates digital inputs by cabinet and circuit. It does not operate the breakers directly.
FEXLINK maintains the device-to-point mapping and displays status and events.
O&M staff review exceptions by cabinet, circuit and area, and complete alarm acknowledgement and inspection records.
Breaker auxiliary contacts, MCB status contacts and cabinet door contacts are wired to E…
ESI Digital Status Monitor · ESX Smart Edge Computing Gateway
Every digital input maps to a unique cabinet, circuit and status meaning
This solution acquires dry contacts only and does not infer the internal cause of a breaker fault
It needs an MCB status auxiliary contact or a digital signal that can be safely connected. Without an auxiliary contact, the retrofit method should be evaluated separately.
No. ESI is used for dry contact status acquisition. Current, power and energy require a suitable electrical parameter monitoring product.
It can be treated as a status or management alarm, but the alarm level, delay and response responsibility must be configured according to site procedures.
They can be grouped by cabinet and connected to ESX over a fieldbus. The specific bus, distance and address plan are confirmed by model and site conditions.
It depends on contact location and site safety measures. A shutdown window, isolation and voltage verification plan must be completed before installation.
Share the application, circuit conditions and existing system interfaces so engineers can confirm selection and implementation boundaries.